TCC coordination studio

Two inverse time overcurrent elements on log log axes, from the GE Multilin 850's own published curve equation. Every trip time here is checked against the 210 published in its manual.

The proof, not the promise

The manual states one of its own cells in prose on p.4-124: an Extremely Inverse curve at TDM = 2, with fault current 5× pickup, "will not occur before 2.59 s". Three independent representations inside that one document agree, and this page computes the third of them live:

RepresentationManual p.4-115 / 4-124This page
Prose worked example2.59 s
Table 4-35 cell2.593 s
Equation + Table 4-342.5934 s

All 210 cells of Table 4-35 are recomputed in verify/verify.js, which is the gate this project shipped behind. 210 of 210 agree; the worst disagreement is 0.135%, which is the table's own rounding to three decimals.

Devices

Curve family: GE Multilin 850, Table 4-34. This tool reproduces one named manufacturer's published curves and claims no standards conformance. GE and SEL both cite IEEE C37.112-1996 over different constants, about 5× apart, and C37.112 itself is gated and unread here.

At the fault current

n/a interval

What this will not tell you

There is no pass and no fail here, deliberately. The customary interval is a rule of thumb its own source words as "usually", and an if statement would turn that into a limit the source declined to state. The band is drawn so you can judge against it. The judgment stays with you.