ATS sequence simulator

Utility fails. Sense, override, engine start, transfer, retransfer, cooldown, on a published vendor's own timers.

Timing chart

normal source emergency source dead / unavailable event this tool cannot size

Sequence

    Scenario

    Generator ready time is a property of the generator set, not of the transfer switch. No ASCO timer governs it, so it is an input here and not a published default.

    Sync check (closed transition)

    Timers (published defaults)

    Every field is bounded by the range the manufacturer publishes for it. A value outside that range is not a setting, so it is refused rather than clamped.

    There is no "the" ATS

    What this tool will not tell you